User Manual
10 PROFIDRIVE MODE The application can be drived in ProfiDrive standard compatible mode (ProfiDrive Mode). Driving mode is selected by using the ap
11 PKW-PART The parameter part (PKW) is fixed to 4 words and can be used for reading and/or updating the parameters in the application one by one. R
12 AKA field meanings (slave → master) Value Function 0 No response 1 Transfer parameter value (word) 2 Transfer parameter value (long word) 3
13 EXAMPLES In the following examples, when you see: Index → you have to refer to LIST OF PARAMETERS chapter; xxxx → don’t care about the word’s v
14 PZD-PART MultiCOM 401 is provided with a default PZD input configuration: DEFAULT PZD INPUT CONFIGURATION DESCRIPTION Unit Index PZD1 UPS s
15 PERMANENT PZD CONFIGURATION PZD configuration can be stored to non-volatile memory and automatically restored at the gateway power up. For this p
16 LIST OF PARAMETERS Parameters can be devided into three categories: 1. UPS parameters (from the range 1-799) 2. Gateway internal parameters (f
17 Index Data type MEASUREMENTS UNIT 1 Unsigned16 UPS states (see the STATES table) Flag 2 Unsigned16 UPS states (see the STATES table) Flag
18 Index Data type NOMINAL DATA UNIT 73÷77 78 Unsigned16 Output nominal voltage (star) V 79 Unsigned16 Output nominal frequency 0.1*Hz 80 Uns
19 GATEWAY INTERNAL PARAMETERS These parameters are used in the ProfiDrive mode Index Data type R/W access Description 802 Unsigned8 Read-wri
20 SCREENSHOT OF MONITORING A MULTICOM 401 IN A PROFIBUS NETWORK
21 CONNECTORS PINOUT PROFIBUS CONNECTOR PIN # DESCRIPTION 1 NC 2 NC 3 RXTX+ 4 RTS 5 GND 6 +5Vdc 7 NC 8 RXTX- 9 NC SERIAL 2 PIN #
22 DIAGNOSTIC LED In the operational mode the meanings of LEDs are: LED Color Description Led RUN Green Regular working Blank UPS communicati
0MNU105NPB
3 INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and bui
4 SUMMARY PRESENTATION ___________________________________________________ 5DESCRIPTION __________________________________________________________
5 PRESENTATION DESCRIPTION MultiCOM 401 allows you to connect the UPS to a Profibus DP network. The device enables to integrate, in industrial envi
6 OPENING THE PACKAGING AND CHECKING THE CONTENTS After opening the packaging, first check the contents. The packaging should contain: MultiCOM 40
7 INSTALLATION AND CONFIGURATION In order to access the DIP-switches and the jumpers, disconnect the device from the power supply, remove the 4 sc
8 BUS TERMINATION AND BIASING MultiCOM 401 is supplied with the bus termination and biasing resistors already mounted internally (R=100Ω). Dip-swit
9 JUMPER SETTINGS For proper working of the device, the jumper have to be set as shown in the figure below. = closed = open CONNECTION TO THE
Kommentare zu diesen Handbüchern